Home / All / Feeder Guide / What to Check Before Restarting a Stored Servo Feeder

What to Check Before Restarting a Stored Servo Feeder

Nov 24,2026

A press cell comes back from six months of shutdown, the main drive starts, and the first coil runs 3 mm short on the first stroke.

Nothing failed during storage. Everything that failed was decided during storage and discovered afterwards.

Servo feeder recommissioning is a short list of checks that most plants run from memory, in the wrong order, after the first bad part.

The feeder data sheets give the reference values for each model. This article gives the sequence.

Six steps, in the order that avoids doing one of them twice, plus the two conditions where no checklist will help.

Six Months Idle Does Six Things to an NC Servo Feeder

Storage is not neutral. Six months of standing still degrades an NC servo feeder in ways that a running machine never experiences, and all of them appear in the first hour of production.

The encoder battery drains whether the machine is powered or not. Drive capacitors lose forming. Feed rolls rust where they touch the strip and flat-spot where they press against each other.

Brake linings take a set. Grease separates into oil and soap, and the soap stays in the gearbox while the oil runs away from the surfaces that needed it.

Hydraulic seals on the pilot release dry out and weep on the first cycle. Every one of those is cheaper to prevent than to discover.

Condensation is the quiet one. A cabinet that cools overnight pulls moisture onto terminal blocks and drive boards, and the damage is done before anyone opens the door in the morning.

Feed rolls flat-spot because the pressure was left on. Two hardened rolls pressed together for six months take a set at the contact line, and that mark transfers to strip on the first run.

Technician inspecting feed rolls on an NC servo feeder before restarting the press cell
Rust at the roll contact line is invisible until a strip runs over it.

Steps 1 to 3: Power, Memory and the Encoder Reference

Power the control on before touching anything mechanical, and let it sit at idle for 24 hours. That is the cheapest capacitor reforming available, and skipping it is how a drive board fails on day one.

Three files should be open before the main power goes on, because each one answers a question that otherwise costs a day to reconstruct.

  • The parameter backup, with its date, so a lost reference can be restored rather than rebuilt
  • The last alarm export, which names what was marginal before the shutdown
  • The battery replacement date from the maintenance log, not the date on the cell

Then read the alarm history before clearing it. A stored overcurrent or position error from the last shift tells you what was marginal before the shutdown, which is usually what fails first after it.

Check the encoder battery voltage under load rather than open circuit. A 3.6 V lithium cell that reads 3.4 V open circuit can sit near 2.9 V once the encoder draws current, and the reference is lost at that point.

If the battery has failed, restore parameters from the backup file and re-home every axis. Do not jog to a remembered position; the reference is gone and the machine does not know where it is.

Steps 4 to 6: Rolls, Brake and Lubrication

  • Rolls: release the pressure before storage, then inspect the contact band for rust and flat spots
  • Brake: measure the release gap, 0.1 to 0.2 mm, and confirm the armature lifts without drag
  • Grease: purge every point, then re-grease to the drawing rather than topping up what is there
  • Pilot release: cycle it ten times dry and look for weeping at the seals before running strip
  • Guides: check side guide clearance against the strip width in the job packet, not against the last job

A rust band 0.1 mm deep across a feed roll is not cosmetic. It changes the effective roll radius at that line, and a 0.1 mm change on a 42 mm roll is 0.24 percent of feed length.

Guide clearance is the last mechanical item and the one that decides whether the first coil tracks. A side guide set for the previous job pushes a narrower strip off centre, and the operator blames the feeder.

The brake gap is the item most often left alone, and the most common reason for a hot motor on day one.

A dragging armature adds load continuously, and the drive reports it as an overload rather than as a brake fault.

What Each Month of Storage Costs in Parts

Time in storageWhat degrades firstWhere it costs you
1 to 3 monthsRoll contact bands, brake take-upHalf a shift of cleaning; no parts cost
3 to 6 monthsEncoder battery margin, grease separationA 20 USD cell, or a full re-home at 2 to 4 hours
6 to 12 monthsDrive capacitors, hydraulic sealsPower-up failures and a weeping cylinder, 300 to 900 USD
Over 12 monthsBearing grease, guide surfaces, roll flat spotsRoll replacement and a re-commissioning week

The jump between six and twelve months is not gradual. Capacitor forming and seal elasticity both pass a point of no return, and the cost moves from consumables to components.

Parts cost is the smaller number in most of these rows. The larger one is the shift that stops while somebody works out why the first part came up short.

If a machine will stand longer than three months, run it for 20 minutes a month under no load. That single habit keeps the battery charged, the grease circulated and the seals wet.

Where This Checklist Cannot Save You

Two conditions defeat the sequence above, and both are common enough to plan for.

The first is a machine stored somewhere it should not have been. An unheated warehouse with a leaking roof condenses water inside the cabinet every night, and no roll inspection finds a corroded terminal block.

The second is a parameter backup that does not exist. If the battery died and nobody kept the file, recommissioning becomes commissioning, with every axis re-tuned from scratch.

On a five-axis servo feeder that is two to three days of an engineer's time, and it is the single most expensive omission in the whole list.

The checklist also assumes the machine was put away correctly. A feeder stored with roll pressure applied develops flat spots that no cleaning removes, and the only fix is a regrind or a new roll set.

Where the arithmetic misleads is in the assumption that a short run proves the machine. Twenty strokes at 30 SPM will not reveal a marginal capacitor or a seal that weeps only when the oil is hot.

The Sign-Off Sheet That Prevents a Repeat

A stored machine is a decision, not an accident. The sheet below turns that decision into a record that the next shift can follow.

CheckPass criterionWhat it protects
Encoder battery under load3.2 V or aboveThe position reference, and 4 hours of re-homing
Roll contact bandNo visible pitting across the working widthFeed length on every job that follows
Brake release gap0.1 to 0.2 mm, armature freeThe drive, which reports a dragging brake as overload
Parameter backupFile dated within the last 12 monthsTwo to three days of commissioning
First-article lengthWithin ±0.05 mm over 20 strokesThe die, which does not survive a short feed

The last row is the one that closes the loop. Twenty strokes at production speed, measured with a tape and a dial, tell you more about the machine than an hour of listening to it.

Sign the sheet at the machine rather than in the office. A record written the next day is a record of what someone remembers, and the details that matter are the ones that get dropped.

The feed accuracy walkthrough sets out how each station contributes to that ±0.05 mm, which makes it obvious which of them a storage period would have damaged.

Does a servo feeder lose its reference after 6 months unpowered?

Assume yes if the encoder is absolute and the battery is over 3 years old. The cell drains slowly even with the control off, and the reference is lost the moment voltage falls under the encoder threshold.

How long should the first production run be after 12 months?

Run 20 to 30 strokes at 30 SPM, measure every fifth part, then step to full speed for 200 strokes. A fault that appears only at temperature will not show up in the first minute.

Is 0.1 mm of rust on a feed roll acceptable?

No. On a 42 mm roll that band changes the effective radius by 0.24 percent, which is 0.24 mm of error on a 100 mm feed, and it marks the strip on every stroke.

What does a dead encoder battery really cost to fix?

A 20 USD cell, plus 2 to 4 hours of re-homing and first-article checks. If no parameter file exists, the same failure costs 2 to 3 days of commissioning instead.

Where to go next

Storage damage surfaces as length error, which is what the feed accuracy cluster measures. Start from the error budget and work back to the station that owns the drift.

Read the feed accuracy error budget